DC Relay and Trip Coil Testing

Direct-current relays and coils are the part of a protection scheme that does the physical work: the trip coil opens the breaker, the close coil closes it, the DC relay blocks or permits a function, and the contactor changes state. All of them are tested with the same basic method: apply a variable DC source, read the contact and time the change. The limits are set by the DC range of the source.

What can be tested

Test object What to measure Method
DC auxiliary relay Pickup voltage, dropout voltage, return coefficient, operating time Voltage ramp up and down with a binary input on the contact
DC contactor Pickup and dropout, contact timing, chatter Voltage ramp and step with contact timing
Trip and close coils Operating current, operating time, minimum operating voltage DC source with current and voltage recorded; binary input on the breaker auxiliary contact
DC under/overvoltage relay Pickup and dropout thresholds, time delay Voltage ramp or step at the relay terminals
DC time relay Delay accuracy Step the coil voltage and time the contact change
Interposing relays and lockout relays Pickup, dropout, manual reset, target Voltage step and contact timing

The DC range and what it covers

Output VAE-430 VAE-660
DC current 3 × ±10 A 6 × ±10 A
DC voltage 3 × ±160 V 6 × ±160 V
DC accuracy ≤ 0.5 % ≤ 0.5 %
DC power 3 × 120 VA at 10 A; 3 × 70 VA at 160 V 6 × 70 VA at 10 A; 6 × 70 VA at 160 V
Auxiliary DC supply 110 / 220 V, max 1.5 A, fixed 110 / 220 V, max 1.5 A, fixed

The programmable DC output covers 24 V, 48 V and 110 V control systems with margin. It does not reach 220 V DC coils. The fixed 110/220 V auxiliary supply can power a relay or a small load, but it is not adjustable, so it cannot be used to find a 220 V coil’s pickup or dropout. For 220 V DC coils, use the station battery with a variable series resistance or a dedicated adjustable DC source, and record the method.

Pickup, dropout and return coefficient

The standard sequence for a DC relay is a slow ramp up to pickup, a hold, then a slow ramp down to dropout. The return coefficient is the dropout value divided by the pickup value. The test set records both transitions through a binary input, so the values come from the same time base. For a trip coil, the important values are the minimum operating voltage, the current at that voltage and the time from energisation to the breaker auxiliary contact change.

Coil current and burden

The DC output records voltage and current, so the coil resistance can be derived at the operating point. That is useful for detecting a coil that is out of tolerance or a circuit with unexpected series resistance. It is not a substitute for a winding resistance measurement at a defined temperature; the coil is a load, not a test specimen with a temperature correction.

What the test set does not do

Item Why
220 V DC coils Programmable DC output stops at ±160 V
DC ground fault relays with a bridge circuit Some schemes need a dedicated bridge or injection unit; check the scheme manual
Breaker mechanical characteristics Travel, velocity and bounce need a breaker analyser
Contact resistance Requires a micro-ohmmeter
1500 V DC traction equipment The DC output is a control-level source, not a traction power source
Coil insulation and withstand Requires an insulation tester

Frequently asked questions

Can the VAE-430 test a 110 V DC trip coil?

Yes. The programmable DC source reaches ±160 V and ±10 A, with 0.5 % accuracy. The binary input records the auxiliary contact and the operating time.

Can it test a 220 V DC coil?

Not from the programmable output. The fixed 110/220 V auxiliary supply is not adjustable. Use the station battery with a variable resistance or a dedicated adjustable source, and document the method.

Does it measure coil resistance?

It records coil voltage and current at the operating point, so resistance can be derived. That is a functional value at the test temperature, not a temperature-corrected winding resistance.

How accurate is the timing?

The VAE-430 records binary events with 0.1 ms resolution; the VAE-660 with ±1 ms. Both are sufficient for DC relay and coil operating times.

Can it test the breaker as well?

It can time the trip and close commands through the breaker auxiliary contacts. Mechanical travel, velocity and contact resistance need a breaker analyser and a micro-ohmmeter.