A protection relay test set is a programmable voltage and current source. What changes from one industry to the next is not the instrument but the test object: an ATS controller in a data center, a motor feeder in a refinery, a collector-system relay in a wind farm, or a protection panel on a builder’s factory floor. This section maps the test object to the injection, the pass criterion and the VA-TEK model that covers it.

One platform, different test objects

VA-TEK relay test sets are used across industry segments. The common requirement is a secondary-injection source with enough channels, power and binary I/O to reproduce the scheme around the relay. The differences are the number of simultaneous voltages and currents, the sequence logic, and the documentation the customer has to hand over.

Industry Typical test objects What decides the model Recommended
Data centers ATS/STS, generator protection, main-tie-main, UPS bypass, feeder relays Two simultaneous three-phase voltage sources for dual-source transfer; six voltage channels VAE-660
Industrial plants Motor feeders, incoming supply, cogeneration, process transformers, capacitor banks Single-ended three-phase injection; occasional 87T differential VAE-430; VAE-660 for differential
Renewable energy Interconnection relays, collector feeders, BESS PCS interface, anti-islanding schemes Voltage and frequency sweeps; six-phase for differential and multi-end schemes VAE-430; VAE-660 for differential
Panel builders Protection panels, switchgear FAT, ATS and control panels, interlocking and trip circuits Multi-vendor relay templates, binary I/O count, repeatable FAT documentation VAE-430; VAE-660 for 8/8 IO and differential
Marine and offshore Generator protection 87G, preferential trip, blackout auto-start, shore connection, switchboard feeders Six current channels for 87G; multi-source sequences for blackout and shore connection VAE-660; VAE-430 for single-ended
Rail and metro AC traction distance and feeder protection, TSS differential, auto-reclosing; DC feeder relays and control-level DC 16.7 Hz from PC mode; six channels for two-end schemes; DC limited to ±160 V / ±10 A VAE-430 or VAE-660; neither does DCCB primary

Device applications: the same instrument, a different test object

Beyond the industry pages, the same source is used on devices that are not protection relays. The common thread is a controller or a coil that expects a voltage, a current, a phase angle or a frequency, and issues a command that has to be timed. The device application pages explain the injection, the pass criterion and the limits for each test object.

Selection in three questions

  1. How many sources must be live at once? A dual-source ATS or a two-end differential needs six voltage or six current channels. A single feeder test needs three current and one to three voltage channels.
  2. What is the highest burden? Electromechanical relays and long leads can load the source. The VAE-660 delivers up to 1000 VA on one phase; the VAE-430 delivers 900 VA on its single-phase parallel output.
  3. How much sequence and I/O? Transfer schemes, interlocking, trip-circuit monitoring and load shedding need binary inputs and outputs. The VAE-430 has 8 inputs and 4 outputs; the VAE-660 has 8 and 8.

What this section is not

Every page here describes secondary-injection testing. The test set injects voltages and currents into the relay terminals; it does not inject primary current, energise a switchgear bus, or certify an inverter. Where a test needs primary injection, a load bank, a class-society witness, or IEC 61850 Sampled Values, the page says so and the scope is handed to the appropriate method or supplier.