Two questions can be asked of an installed cable. The first is whether it will hold a voltage right now — a proof test. The second is what condition it is in — a diagnosis. A withstand test answers the first; tan delta and partial discharge answer the second. They are not substitutes, and the most common mistake is to run one and act as if it answered the other.
This article sets out when a plain withstand is enough, when a diagnostic is worth the extra time, and how a monitored withstand combines the two without over-stressing an ageing cable.
Key takeaways
- A withstand is a proof test: it says the cable held, not that it is sound.
- A diagnostic (tan delta, PD) gives condition, but is not on its own a pass/fail gate.
- Every withstand applies stress, and on aged cable that stress has a cost — the question is whether the reassurance is worth it.
- A monitored withstand runs the proof test while watching tan delta and PD, and aborts if the trend turns — proof on demand, diagnosis for free.
- Let cable age and criticality, not habit, drive the choice.
1. The two questions
A withstand test raises the cable to a test voltage, holds it for a set time, and records whether it survived. The output is binary: pass or fail. It is a proof that at that moment, at that voltage, the insulation held.
A diagnostic measures a property that changes with the condition of the insulation — dielectric loss (tan delta) or partial discharge — and the output is a value to be interpreted, often against the cable’s own history. It is information about how the cable is aging, not a verdict.
The gap between them is where most testing mistakes live. A cable can pass a withstand and fail soon after, because the degradation is distributed (water trees) rather than a single bridging defect. A cable can show a high diagnostic reading and run for years, because the reading is within its normal band. Neither result alone is the whole story.
2. The cost of a withstand on aged cable
A withstand test is not free of consequence. The test voltage is, by design, higher than operating voltage, and it is applied for minutes rather than milliseconds. On new cable that is exactly the point. On aged cable it is a stress event: insulation that is already degraded gets driven toward its limit, and there is a real, if small, chance of failing a cable that might otherwise have continued to serve.
This is not an argument against withstand testing. It is an argument for choosing the voltage deliberately and for knowing what you are testing for. A maintenance withstand on a thirty-year-old cable, at a level chosen to be defensible rather than impressive, is a reasonable proof. The same cable at a new-installation acceptance level is a different risk. See VLF test voltage selection for how the level is set.
3. What the diagnostics add
Two diagnostics are commonly run with a VLF set:
| Diagnostic | Measures | Strong at | Weak at |
|---|---|---|---|
| Tan delta | Dielectric loss — the resistive current relative to the capacitive current | Detecting moisture and distributed ageing; trending across outages | Giving an absolute pass/fail number; it moves with temperature and voltage |
| Partial discharge | Localised discharge at defects | Locating a defect in a joint or termination | Grading diffuse ageing; producing values transferable to power frequency |
Run together, they cover different failure modes: tan delta sees the diffuse and the moisture-driven, PD sees the localised and the point-defect. For detail, see VLF tan delta testing and VLF partial discharge testing.
4. The monitored withstand
A monitored withstand is the compromise that gets a proof test and a diagnosis in one pass. The test voltage is raised and held as in a normal withstand, but throughout the hold the set monitors tan delta, leakage current and partial discharge, and the operator watches for a trend rather than only for a trip.
The value of this is threefold:
- No extra stress. The diagnostics ride on the withstand that was going to be applied anyway. There is no second test at a second voltage.
- Early warning. A rising tan delta or a growing PD level during the hold is visible before the cable trips, so a marginal cable can be brought down deliberately instead of failing at full voltage.
- A richer record. The report carries the condition trend as well as the pass/fail, which is what makes the next outage’s numbers meaningful.
For aged or critical circuits this is usually the better default than a bare withstand: it keeps the proof test but recovers the diagnostic information that a plain withstand throws away.
5. Choosing
| Situation | Reasonable default |
|---|---|
| New cable, acceptance | Withstand at the acceptance level; add PD if the owner wants a baseline |
| In-service, early life, low criticality | Withstand at maintenance level |
| In-service, aged, water-tree-prone XLPE | Monitored withstand, or diagnostic-led with a reduced withstand |
| After repair | Withstand at controlled level plus PD to confirm the repair |
| Critical circuit, trend history exists | Monitored withstand; compare against previous readings |
Habit — running the same test on every cable because that is what the procedure says — is the thing to avoid. The test should match the cable in front of you and the question the outage is meant to answer.
6. The short version
A withstand proves; a diagnostic informs. When the cable is new or low-risk, a defensible withstand is enough. When the cable is old, critical, or prone to ageing you cannot see, run a monitored withstand: it proves the cable and reads its condition in the same test, and it gives the operator a reason to stop before the cable does. The closing sequence after a repair builds on these same choices — see VLF testing after cable repair.
Frequently asked questions
What is the difference between a withstand and a diagnostic test?
A withstand is pass/fail: the cable holds the voltage for the duration or it does not. A diagnostic such as tan delta or partial discharge measures condition and can be tracked over time. They answer different questions.
Is a withstand harmful to aged cable?
A withstand applies a defined stress, and on aged cable that stress is a real consideration. A diagnostic is often the better first question because it informs a decision without committing the cable to the same level of stress.
What is a monitored withstand?
A withstand in which measured quantities – tan delta and partial discharge – are watched across the hold. Under IEEE 400.2-2024 the judging criteria are these measures, not only whether the cable survived.