VLF-34TD 34 kV VLF Hipot & Tan-Delta Diagnostic Test Set

Single-unit 34 kV VLF system combining withstand, tan-delta diagnostics, DC and sheath test with fault location for 5–15 kV cable.

VLF sine wave output 0 – 34 / 0 – 24
DC output ± 0 – 34
Output current 0 – 14
Output frequencies 0.1 / 0.05 / 0.02 / 0.01
Tan-delta accuracy 1.0 × 10⁻⁴
Weight 22
Model comparison
Specification VLF-34TD VLF-45TD
VLF sine wave output (peak / RMS) kV peak / kV RMS 0 – 34 / 0 – 24 0 – 45 / 0 – 31.8
DC output kV ± 0 – 34 ± 0 – 45
Output current mA 0 – 14 0 – 14
Output frequencies Hz 0.1 / 0.05 / 0.02 / 0.01 0.1 / 0.05 / 0.02 / 0.01
Tan-delta accuracy 1.0 × 10⁻⁴ 1.0 × 10⁻⁴
Tan-delta load range µF 5 nF – 10 5 nF – 10
Sheath test voltage kV 10 10
Sheath test current mA 0.1 – 5.0 0.1 – 5.0
Capacitance range / accuracy 0 – 18.0 µF · typ. 20 % 0 – 18.0 µF · typ. 20 %
Internal memory 128 test records 128 test records
Dimensions (L × W × H) mm 510 × 310 × 480 510 × 310 × 480
Weight kg 22 23
Power supply AC 100 – 240 V, 1-phase, 50/60 Hz AC 100 – 240 V, 1-phase, 50/60 Hz
Operating temperature °C −10 … +50 −10 … +50
Humidity ≤ 90 % RH ≤ 90 % RH

Technical Specifications

Specification Value Unit
Output
VLF sine wave 0 – 34 kV peak / 0 – 24 kV AC RMS · resolution ± 0.1 kV · accuracy ± 1 %
VLF square wave 0 – 34 kV peak · resolution ± 0.1 kV · accuracy ± 1 %
DC (proof test, sheath test) ± 0 – 34 kV · resolution ± 0.1 kV · accuracy ± 1 %
Output current 0 – 14 mA · resolution 1 µA · accuracy ± 1 %
Output frequency 0.1 / 0.05 / 0.02 / 0.01 Hz
Sheath Test
Maximum voltage 10 kV
Test current 0.1 – 5.0 mA
Sheath Fault Location
Maximum voltage 10 kV
Pulse / period modes 1:3 / 4 s · 1:5 / 4 s · 1:5 / 6 s · 1:9 / 6 s
Tan-Delta (TD) Test
Frequency 0.1 / 0.05 / 0.02 / 0.01 Hz
Load range 5 nF – 10 µF
TD range 0.01 … 999.99 × 10⁻³
Accuracy 1.0 × 10⁻⁴
Resolution 1.0 × 10⁻⁵
Capacitance & Resistance Measurement
Capacitance range / accuracy 0 – 18.0 µF · typ. 20 %
Resistance range / accuracy 0.1 – 20 GΩ · typ. 10 %
Memory & Interface
Internal memory 128 test records
Interface USB (data export, firmware update)
Mechanical
Dimensions (L × W × H) 510 × 310 × 480 mm
Weight 22 kg
Design Single integrated unit
Power Supply & Environment
Power supply AC 100 – 240 V, 1-phase, 50/60 Hz
Operating temperature −10 … +50 °C
Storage temperature −20 … +70 °C
Humidity ≤ 90 % RH

Key Features

Four-in-one cable test system

VLF withstand, tan-delta diagnostics, DC proof test and sheath test with fault location in one integrated 22 kg unit.

VLF sine wave to 34 kV peak

0 – 34 kV peak / 0 – 24 kV AC RMS output with four frequencies from 0.1 Hz to 0.01 Hz.

Square wave and DC modes

0 – 34 kV peak square wave and ± 0 – 34 kV DC for special applications and proof/sheath tests.

Integrated tan-delta diagnostics

TD accuracy 1.0 × 10⁻⁴ and resolution 1.0 × 10⁻⁵ over a 5 nF – 10 µF load for water-tree ageing assessment.

Sheath test & fault location

Up to 10 kV sheath test at 0.1 – 5.0 mA with selectable fault-location pulse modes.

USB export & firmware update

128 internal test records exportable to a PC via USB for report generation; firmware updated via USB.

Field-friendly single unit

Runs from 100 – 240 V AC with no external PC needed; sized for one-case site deployment.

Partial discharge diagnostics option

Add the VLF-PD34 to measure partial discharge and localize defects to within 1 % of cable length — 1 pC sensitivity, up to 20 km measuring range.

Applications

5–15 kV cable testing

Installation, acceptance and maintenance testing of shielded power cable in the 5 kV to 15 kV class.

Tan-delta condition assessment

Diagnosing water-tree ageing in aged XLPE/EPR circuits by voltage-dependent dielectric loss.

Monitored withstand testing

Step-test and monitored-withstand protocols for cable insulation with suspect condition.

Sheath integrity & fault location

Testing cable oversheaths and locating sheath-to-earth faults per IEC 60229.

DC proof testing

DC proof tests on cable systems and accessories.

Standard Accessories

  • VLF-PD34 Partial Discharge Diagnostics System

Frequently Asked Questions

What does tan-delta (TD) testing add over a plain VLF hipot test?

A VLF withstand test only shows whether a cable breaks down at a given voltage. Tan-delta diagnostics measure dielectric loss and, crucially, how it changes as voltage is stepped. A rising tan-delta with voltage is a classic indicator of water-tree ageing in XLPE insulation, so TD testing can flag a marginal cable before it fails.

Which cable classes is the VLF-34TD intended for?

The VLF-34TD is positioned for installation, acceptance and maintenance testing of shielded power cable in the 5 kV to 15 kV class. Its 34 kV peak output covers the test voltages these circuits require under IEEE 400.2.

Can the sheath fault-location mode pinpoint the exact fault position?

The VLF-34TD applies sheath test and fault-location pulse modes to condition and pre-locate sheath-to-earth faults. Precise distance-to-fault on the route is normally completed with a dedicated cable fault locator / path tracer.

Does it test VLF, tan-delta and DC with a single connection?

Yes. One test set performs VLF withstand, tan-delta diagnostic and DC proof tests on the cable, plus sheath test and fault location on the oversheath, with results stored internally and exported via USB.

Can this set run partial discharge diagnostics?

Yes — with the VLF-PD34 partial discharge diagnostics add-on, which is currently supported on the VLF-34TD and VLF-45TD. It detects partial discharge down to 1 pC and localizes the source to within 1 % of cable length over runs up to 20 km.