VLF-PD34
The VLF-PD34 is a partial discharge (PD) diagnostics unit used together with a VLF generator. It measures PD…
- Operating voltage 1 – 24 / 34
- Rated current 1
- Coupling capacitor 1
Single-unit 45 kV VLF system combining withstand, tan-delta diagnostics, DC and sheath test with fault location for 5–25 kV cable in installation and maintenance testing.
| Specification | VLF-34TD | VLF-45TD |
|---|---|---|
| VLF sine wave output (peak / RMS) kV peak / kV RMS | 0 – 34 / 0 – 24 | 0 – 45 / 0 – 31.8 |
| DC output kV | ± 0 – 34 | ± 0 – 45 |
| Output current mA | 0 – 14 | 0 – 14 |
| Output frequencies Hz | 0.1 / 0.05 / 0.02 / 0.01 | 0.1 / 0.05 / 0.02 / 0.01 |
| Tan-delta accuracy | 1.0 × 10⁻⁴ | 1.0 × 10⁻⁴ |
| Tan-delta load range µF | 5 nF – 10 | 5 nF – 10 |
| Sheath test voltage kV | 10 | 10 |
| Sheath test current mA | 0.1 – 5.0 | 0.1 – 5.0 |
| Capacitance range / accuracy | 0 – 18.0 µF · typ. 20 % | 0 – 18.0 µF · typ. 20 % |
| Internal memory | 128 test records | 128 test records |
| Dimensions (L × W × H) mm | 510 × 310 × 480 | 510 × 310 × 480 |
| Weight kg | 22 | 23 |
| Power supply | AC 100 – 240 V, 1-phase, 50/60 Hz | AC 100 – 240 V, 1-phase, 50/60 Hz |
| Operating temperature °C | −10 … +50 | −10 … +50 |
| Humidity | ≤ 90 % RH | ≤ 90 % RH |
Prepare the test before you leave the office. These browser-based calculators match this instrument and need no account.
| Specification | Value | Unit |
|---|---|---|
| Output | ||
| VLF sine wave | 0 – 45 kV peak / 0 – 31.8 kV AC RMS · resolution ± 0.001 kV · accuracy ± 1 % | |
| VLF square wave | 0 – 45 kV peak · resolution ± 0.001 kV · accuracy ± 1 % | |
| DC (proof test, sheath test) | ± 0 – 45 kV · resolution ± 0.001 kV · accuracy ± 1 % | |
| Output current | 0 – 14 mA · resolution 1 µA · accuracy ± 1 % | |
| Output frequency | 0.1 / 0.05 / 0.02 / 0.01 | Hz |
| Load Rating | ||
| @ 0.1 Hz | 0.5 µF @ 45 kV peak | |
| @ 0.05 Hz | 1.0 µF @ 45 kV peak | |
| @ 0.01 Hz | 5.0 µF @ 45 kV peak | |
| Sheath Test | ||
| Maximum voltage | 10 | kV |
| Test current | 0.1 – 5.0 | mA |
| Sheath Fault Location | ||
| Maximum voltage | 10 | kV |
| Pulse / period modes | 1:3 / 4 s · 1:5 / 4 s · 1:5 / 6 s · 1:9 / 6 s | |
| Tan-Delta (TD) Test | ||
| Frequency | 0.1 / 0.05 / 0.02 / 0.01 | Hz |
| Load range | 5 nF – 10 | µF |
| TD range | 0.01 … 999.99 × 10⁻³ | |
| Accuracy | 1.0 × 10⁻⁴ | |
| Resolution | 1.0 × 10⁻⁵ | |
| Capacitance & Resistance Measurement | ||
| Capacitance range / accuracy | 0 – 18.0 µF · typ. 20 % | |
| Resistance range / accuracy | 0.1 – 20 GΩ · typ. 10 % | |
| Memory & Interface | ||
| Internal memory | 128 test records | |
| Interface | USB (data export, firmware update) | |
| Mechanical | ||
| Dimensions (L × W × H) | 510 × 310 × 480 | mm |
| Weight | 23 | kg |
| Design | Single integrated unit | |
| Power Supply & Environment | ||
| Power supply | AC 100 – 240 V, 1-phase, 50/60 Hz | |
| Operating temperature | −10 … +50 | °C |
| Storage temperature | −20 … +70 | °C |
| Humidity | ≤ 90 % RH | |
VLF withstand, tan-delta diagnostics, DC proof test and sheath test with fault location in one integrated 23 kg unit.
0 – 45 kV peak / 0 – 31.8 kV AC RMS output with four frequencies from 0.1 Hz to 0.01 Hz.
0 – 45 kV peak square wave and ± 0 – 45 kV DC for special applications and proof/sheath tests.
TD accuracy 1.0 × 10⁻⁴ and resolution 1.0 × 10⁻⁵ over a 5 nF – 10 µF load for condition assessment of cable insulation.
Up to 10 kV sheath test at 0.1 – 5.0 mA with selectable fault-location pulse modes.
128 internal test records exportable via USB for reports; firmware updated via USB.
Runs from 100 – 240 V AC with no external PC; a one-case solution for 5–25 kV cable programs.
Add the VLF-PD34 to measure partial discharge and localize defects to within 1 % of cable length — 1 pC sensitivity, up to 20 km measuring range.
Installation and maintenance testing of shielded power cable across the 5 kV to 25 kV class; acceptance testing up to the set's 31.8 kV rms sine ceiling, which covers acceptance levels through the 20 kV class.
Water-tree ageing screening of medium-voltage XLPE/EPR circuits by voltage-dependent dielectric loss.
Diagnostic withstand protocols for cables with suspect insulation.
Testing cable oversheaths and locating sheath-to-earth faults per IEC 60229.
DC proof tests on cable systems and accessories.
The 45 kV peak output extends coverage to cable classes up to roughly 25 kV, whereas the 34 kV model is aimed at 5–15 kV cable. The higher rating also provides margin when the specified test voltage is above 34 kV.
By measuring tan delta at several voltage steps, the instrument detects the voltage-dependent loss that indicates water-tree ageing. Circuits can be ranked by condition so maintenance effort is directed at the cables most at risk.
Yes. The instrument performs VLF withstand, tan-delta diagnostic and DC proof tests, plus sheath test/fault location, and stores up to 128 records for USB export into reports.
The VLF-45TD applies sheath test voltage and selectable fault-location pulse modes up to 10 kV to condition and pre-locate sheath-to-earth faults. Precise route pinpointing is normally completed with a dedicated cable fault locator / path tracer.
Yes — with the VLF-PD34 partial discharge diagnostics add-on, which is currently supported on the VLF-34TD and VLF-45TD. It detects partial discharge down to 1 pC and localizes the source to within 1 % of cable length over runs up to 20 km.