VLF-30-90
The VLF-30-90 family covers the 30, 40, 50, 60, 80 and 90 kV peak sinusoidal VLF hipot test…
- Output voltage range 30 – 90
- Output current 0 – 30
- Output frequencies 0.1 / 0.05 / 0.02 / 0.01
Add partial discharge detection and fault localization to VLF-34TD and VLF-45TD testing — 1 pC sensitivity, defects located to within 1 % of cable length on runs up to 20 km.
| Specification | Value | Unit |
|---|---|---|
| Operating | ||
| Operating voltage | 1 – 24 kV RMS / 34 kV peak at 0.1 Hz | |
| Rated current | 1 | A |
| High-voltage coupling capacitor | 1 | nF |
| Maximum withstand voltage | 68 | kV |
| Excitation | Pure sinusoidal, combined with VLF generator | |
| PD Localization | ||
| Measuring range | 20,000 m at 80 m/µs propagation | |
| Sampling rate | 125 | MHz |
| Localization accuracy | 1 % of cable length | |
| Resolution | ≤ 1 pC / ≤ 1 m | |
| Compatibility | ||
| Supported VLF test sets | VLF-34TD and VLF-45TD (current support) | |
| Tan-delta diagnostics | Available in combination with VLF-34TD / VLF-45TD | |
| Mechanical | ||
| Weight | 18.4 | kg |
| Dimensions | 310 × 260 × 750 | mm |
Measures PD in cable insulation and pinpoints the source, separating cable-body defects from joint and termination defects.
Resolves discharge down to 1 pC with 1 m distance resolution.
Places the discharge site within 1 % of cable length over runs up to 20 km.
High-voltage coupling capacitor rated for 68 kV maximum withstand voltage.
With the VLF generator it applies a pure sinusoidal 1 – 24 kV RMS / 34 kV peak output at 0.1 Hz.
Current supported hosts; in that combination tan-delta diagnostics can also be performed.
PD measurement on newly installed or repaired shielded cable, alongside the VLF withstand test.
Localizing discharge at cable accessories, where a large share of circuit defects occurs.
Periodic PD measurement to trend insulation condition on in-service circuits.
Current supported hosts; the PD unit works with the VLF set and its generator output.
At present the VLF-PD34 is supported with the VLF-34TD and VLF-45TD VLF hipot test sets. It is used together with the VLF generator; the other models in the VLF-30-90 range are not supported at this time.
Detection establishes whether discharge is present and its magnitude, down to 1 pC. Localization uses the propagation velocity (80 m/µs) to place the source on the cable run within 1 % of the cable length, with 1 m resolution and over a measuring range of up to 20,000 m.
PD diagnostics are provided by the VLF-PD34. Tan-delta diagnostics are performed when the unit is combined with the VLF-34TD or VLF-45TD, which carry the tan-delta function.
1 – 24 kV RMS / 34 kV peak at 0.1 Hz, with a rated current of 1 A and a 1 nF coupling capacitor. The coupling capacitor withstands up to 68 kV.
The unit weighs 18.4 kg and measures 310 × 260 × 750 mm.