VLF-PD34 Partial Discharge Diagnostics System for VLF Hipot Test Sets

Add partial discharge detection and fault localization to VLF-34TD and VLF-45TD testing — 1 pC sensitivity, defects located to within 1 % of cable length on runs up to 20 km.

Operating voltage 1 – 24 / 34
Rated current 1
Coupling capacitor 1
Max. withstand voltage 68
Sampling rate 125
Weight 18.4

Overview

Technical Specifications

Specification Value Unit
Operating
Operating voltage 1 – 24 kV RMS / 34 kV peak at 0.1 Hz
Rated current 1 A
High-voltage coupling capacitor 1 nF
Maximum withstand voltage 68 kV
Excitation Pure sinusoidal, combined with VLF generator
PD Localization
Measuring range 20,000 m at 80 m/µs propagation
Sampling rate 125 MHz
Localization accuracy 1 % of cable length
Resolution ≤ 1 pC / ≤ 1 m
Compatibility
Supported VLF test sets VLF-34TD and VLF-45TD (current support)
Tan-delta diagnostics Available in combination with VLF-34TD / VLF-45TD
Mechanical
Weight 18.4 kg
Dimensions 310 × 260 × 750 mm

Key Features

Partial discharge detection and localization

Measures PD in cable insulation and pinpoints the source, separating cable-body defects from joint and termination defects.

1 pC sensitivity, 1 m resolution

Resolves discharge down to 1 pC with 1 m distance resolution.

Localization to 1 % of cable length

Places the discharge site within 1 % of cable length over runs up to 20 km.

1 nF coupling capacitor, 68 kV withstand

High-voltage coupling capacitor rated for 68 kV maximum withstand voltage.

Stable sinusoidal 0.1 Hz excitation

With the VLF generator it applies a pure sinusoidal 1 – 24 kV RMS / 34 kV peak output at 0.1 Hz.

Built for the VLF-34TD and VLF-45TD

Current supported hosts; in that combination tan-delta diagnostics can also be performed.

Applications

Cable acceptance PD testing

PD measurement on newly installed or repaired shielded cable, alongside the VLF withstand test.

Joint and termination diagnostics

Localizing discharge at cable accessories, where a large share of circuit defects occurs.

Maintenance PD surveys

Periodic PD measurement to trend insulation condition on in-service circuits.

VLF-34TD and VLF-45TD users

Current supported hosts; the PD unit works with the VLF set and its generator output.

Frequently Asked Questions

Which VLF test sets does the VLF-PD34 work with?

At present the VLF-PD34 is supported with the VLF-34TD and VLF-45TD VLF hipot test sets. It is used together with the VLF generator; the other models in the VLF-30-90 range are not supported at this time.

What is the difference between PD detection and PD localization?

Detection establishes whether discharge is present and its magnitude, down to 1 pC. Localization uses the propagation velocity (80 m/µs) to place the source on the cable run within 1 % of the cable length, with 1 m resolution and over a measuring range of up to 20,000 m.

Can the VLF-PD34 perform tan-delta diagnostics?

PD diagnostics are provided by the VLF-PD34. Tan-delta diagnostics are performed when the unit is combined with the VLF-34TD or VLF-45TD, which carry the tan-delta function.

What voltage does the PD system operate at?

1 – 24 kV RMS / 34 kV peak at 0.1 Hz, with a rated current of 1 A and a 1 nF coupling capacitor. The coupling capacitor withstands up to 68 kV.

How is the unit transported?

The unit weighs 18.4 kg and measures 310 × 260 × 750 mm.