VLF Test Set Selector — Cable Load, Test Current and Frequency
Voltage class tells you which set can reach the test voltage. It does not tell you whether the set can hold it. A 30 kV set and a 30 kV cable are not the same problem if that cable is eight kilometres long — the cable is a capacitor, and the current needed to swing it charges with length, capacitance and test frequency. This selector works that side of the question: it takes the cable you actually have and returns the burden current, the apparent power and the sets that can drive it to the required voltage.
Key takeaways
- The load on a VLF set is I = 2πfCU. Cable length and capacitance set C, the test voltage sets U, and the output frequency sets f.
- Lower frequency is a lever, not a compromise in voltage. Dropping from 0.1 Hz to 0.02 Hz cuts the burden current by five with the test voltage unchanged.
- Every VA-TEK set is rated in kV peak and mA peak; Table 3 of IEEE 400.2-2024 is in kV rms. The selector converts between them so the cable and the equipment are compared in the same units.
- The 30–90 kV sine sets carry 30 mA peak; the tan delta sets carry 14 mA peak and reach lower voltage. More capability does not always mean more load range.
- Paper-insulated lead-covered cable commonly runs at about twice the capacitance of XLPE at the same voltage. A set that is comfortable on new XLPE may be at its limit on old PILC.
1. What this selector answers — and what it does not
There are two separate VLF questions and they are usually asked in the wrong order.
The first is what voltage do I apply. That is a lookup against the standard, and the VLF test voltage calculator answers it: cable class, test class and waveform in, kV rms and kV peak out.
The second is can my set deliver that voltage into this cable. That is a load calculation, and it is the one that sinks projects. A set can be inside its voltage rating and still trip on over-current a few seconds into the run, because a long cable at 0.1 Hz draws more current than the set can source at the required peak voltage.
This page does the second calculation. It reports the burden current at the test voltage, the apparent power the set has to supply, which models in the range can cover it, and what each lower frequency would buy you if none of them can.
It is a selection aid, not a test procedure. It does not decide whether VLF is the right test for a given cable, does not cover damped AC (that is IEEE 400.4), and does not override a utility or manufacturer specification. Where a specification sets the test voltage and the frequency, the specification governs.
2. VLF test set selector
Default for 15 kV XLPE. Edit to match the cable datasheet.
Test voltage: IEEE 400.2-2024, Table 3 (kV rms, phase to earth). Set ratings: VA-TEK VLF data sheets (kV peak, mA peak). Capacitance defaults are typical XLPE figures, not a substitute for the cable datasheet. Confirm against the governing specification before issuing a procedure.
3. How the current is calculated
A cable under VLF test is a capacitor with the conductor on one plate and the screen on the other. The current the set must supply is the charging current of that capacitor:
I = 2π f C U
Three inputs, and each one behaves differently.
- C is the cable. C = capacitance per kilometre × length. A 6 km run of 0.30 µF/km cable is 1.8 µF, and the set has to move charge into all of it.
- U is the test voltage from Table 3 — not the system voltage. A 15 kV cable tested to acceptance sits at 21 kV rms, which is 29.7 kV peak.
- f is the output frequency, and it is the only term you can change without changing the test.
Worked example. 15 kV XLPE, acceptance, sinusoidal: Table 3 gives 21 kV rms, so 29.7 kV peak. Two kilometres at 0.30 µF/km is 0.6 µF. At 0.1 Hz the peak charging current is 2π × 0.1 × 0.6 × 29.7 = 11.2 mA peak. The same set on eight kilometres of the same cable would need 44.8 mA peak — past the 30 mA rating of every set in the series, and the run would trip on over-current rather than complete. Drop to 0.05 Hz and the requirement falls to 22.4 mA, which a VLF-30 covers comfortably.
That is the whole reason the frequency selector exists in the product rather than being fixed at 0.1 Hz.
4. Why 0.02 Hz and 0.01 Hz exist
The test voltage does not change with frequency. IEEE 400.2-2024 tabulates the withstand level for the cable class and the test class, and it holds whether you run 60 minutes at 0.1 Hz or 60 minutes at 0.02 Hz. What changes is how much charge the set has to move per second, and that scales linearly.
| Frequency | Current vs 0.1 Hz | Seconds per cycle | Cycles in a 60 min test |
|---|---|---|---|
| 0.1 Hz | 1.00× | 10 | 360 |
| 0.05 Hz | 0.50× | 20 | 180 |
| 0.02 Hz | 0.20× | 50 | 72 |
| 0.01 Hz | 0.10× | 100 | 36 |
Two things move at once when you lower the frequency, and they pull in opposite directions. The burden falls in proportion — a long cable that would overload the set at 0.1 Hz becomes testable at 0.02 Hz. The number of cycles in the test falls with it: a 60 minute run at 0.01 Hz puts only 36 cycles on the insulation against 360 at 0.1 Hz. IEEE 400.2 recognises this and sets the duration in minutes rather than cycles for exactly that reason, but the two figures are worth keeping in view when a specification calls for a particular frequency.
Practical rule of thumb: run the highest frequency the set can sustain at the required voltage, and step down only when the cable forces it.
5. Cable capacitance is the number that decides
Length is obvious; capacitance per kilometre is the term people leave at a guess. It moves by a factor of two across a normal cable population before you even get to the insulation type.
| Cable class | Typical capacitance (µF/km) | What moves it |
|---|---|---|
| 6–15 kV | 0.25–0.45 | Three-core construction, insulation wall, conductor size |
| 20–35 kV | 0.15–0.30 | Single-core screening, insulation wall |
| 46–69 kV | 0.12–0.20 | Insulation wall dominates; longer runs of single-core |
| 90–138 kV | 0.08–0.15 | Thick wall, large conductor, single-core |
Paper-insulated lead-covered cable (PILC) sits well above these figures — commonly about twice the XLPE value at the same voltage class, and sometimes more. That matters in maintenance testing, where the cable is more likely to be PILC: the set that handled the acceptance test on new XLPE will be near its limit on the same run twenty years later.
If the number is not on the datasheet, it can be measured. A tan delta set reports capacitance directly as part of its measurement, and the value it prints at the start of a test is the value this selector wants. Failing that, a capacitance bridge reading at low voltage is sufficient — the figure does not change meaningfully between the bridge voltage and the test voltage.
| Cable class | Acceptance test voltage | Maximum length at 0.1 Hz | Maximum length at 0.02 Hz |
|---|---|---|---|
| 11 kV, 0.35 µF/km | 16 kV rms / 22.6 kV peak | ~6.0 km | ~30 km |
| 15 kV, 0.30 µF/km | 21 kV rms / 29.7 kV peak | ~5.4 km | ~27 km |
| 33 kV, 0.18 µF/km | 42 kV rms / 59.4 kV peak | ~4.5 km | ~22 km |
Lengths assume the 30 mA peak rating of the VLF-30-90 series, sinusoidal output, and the capacitance shown. Run the numbers for your own cable above — a different capacitance per kilometre moves these figures by more than the frequency does.
6. Sine and cosine-rectangular place different demands
Both waveforms are recognised by IEEE 400.2-2024, and each has its own table of test voltages, because the peak-to-rms relationship differs between them. That part is handled by the voltage lookup.
On the load side, the difference is in how the current arrives rather than how much charge moves. A sinusoidal source draws a continuous charging current spread over the whole cycle. A cosine-rectangular source charges the cable from one polarity to the other during a short transition, then holds, so the same charge arrives as a shorter and higher-current pulse. The set’s DC supply and its peak-current rating are what absorb that pulse.
The figures in this selector are computed for the sinusoidal case at the selected frequency, and for cosine-rectangular they use the peak voltage the standard’s own table calls for. Treat them as a comparison baseline: for a cosine-rectangular run, confirm the crest current against the set’s datasheet rather than assuming the sine figure transfers directly.
Tan delta and partial discharge measurement, in practice, require the sinusoidal waveform — the diagnostic methods are built on a defined fundamental. A cosine-rectangular output is a withstand-only waveform.
7. The VA-TEK range, by load rating
Two things limit a set: how much voltage it produces and how much current it can push at that voltage. The eight models in the range trade these differently.
| Model | Output rating | Cable class served | Notes |
|---|---|---|---|
| VLF-30 | 30 kV peak / 21.2 kV rms, 30 mA peak | 5–15 kV | Entry model; widest load margin per kV in the range |
| VLF-34TD | 34 kV peak / 24 kV rms, 14 mA peak | 5–15 kV | Adds tan delta, DC and sheath test with fault location |
| VLF-40 | 40 kV peak / 28.3 kV rms, 30 mA peak | 5–20 kV | Withstand only, full 30 mA load |
| VLF-45TD | 45 kV peak / 31.8 kV rms, 14 mA peak | 5–25 kV | Adds tan delta, DC and sheath test with fault location |
| VLF-50 | 50 kV peak / 35.4 kV rms, 30 mA peak | 5–25 kV | Withstand only, full 30 mA load |
| VLF-60 | 60 kV peak / 42.4 kV rms, 30 mA peak | 5–33 kV | Withstand only, full 30 mA load |
| VLF-80 | 80 kV peak / 56.6 kV rms, 30 mA peak | 5–35 kV | Withstand only, full 30 mA load |
| VLF-90 | 90 kV peak / 63.6 kV rms, 30 mA peak | 5–46 kV | Top of the sine range; reaches 46 kV cable at acceptance |
The trade-off is visible in the table: the tan delta models reach 34 and 45 kV but carry 14 mA peak rather than 30 mA peak, because the measuring circuit and the loss-angle instrumentation constrain what the source can supply. If the job is a withstand test on a long cable, the 30 mA models are the right tool. If the job is diagnosis on a shorter run, the TD models add the measurement.
All models operate at 0.1, 0.05, 0.02 and 0.01 Hz. That four-step range is what makes the load rating elastic — the same set covers five times the cable length at 0.02 Hz that it covers at 0.1 Hz.
Full range: VA-TEK VLF hipot testers · VLF-30-90 series · VLF-34TD · VLF-45TD
8. Frequently asked questions
How long a cable can a VLF test set test?
It depends on three things at once: the test voltage for the cable class, the capacitance per kilometre of the cable, and the frequency you run at. A 30 mA set testing 15 kV XLPE at acceptance covers about 5.4 km at 0.1 Hz and about 27 km at 0.02 Hz. There is no single length figure that applies across voltage classes, which is why the selector asks for all three.
Why does lowering the frequency let me test a longer cable?
The charging current is 2πfCU, so it falls in direct proportion to frequency. The test voltage is unchanged, and the test duration is set in minutes rather than cycles, so the insulation still sees the full withstand level for the full hold time. Lowering the frequency is the standard way to extend a set’s reach.
Is 0.1 Hz always better than 0.02 Hz?
0.1 Hz is the conventional test frequency and gives the most cycles in a fixed duration, so it is the default choice. Drop to a lower frequency only when the cable’s capacitance would otherwise overload the set, or when the governing specification calls for it. Where both are permitted, run the higher frequency.
What is the current rating of a VLF test set?
VA-TEK sets are rated in mA peak at the rated output voltage: 30 mA peak for the VLF-30 to VLF-90 withstand models, 14 mA peak for the VLF-34TD and VLF-45TD tan delta models. Compare this with the peak charging current, not the rms figure, because the set’s own display and rating are in peak terms.
Can I test a three-phase cable as a single circuit?
Each core is tested against the screen, and the capacitance that loads the set is the capacitance of the core under test. On a three-core cable the remaining cores are normally earthed, which adds a small amount of mutual capacitance but does not change the calculation materially. Use the capacitance per kilometre for a single core to earth, from the datasheet.
Does this cover damped AC (DAC) or oscillating wave testing?
No. This selector covers continuous VLF under IEEE 400.2-2024. Damped AC is governed by IEEE 400.4, which is currently inactive and reserved, and the load behaviour of an oscillating wave is a different calculation. See VLF versus oscillating wave testing.
What if no set in the range covers my cable?
Three options, in order of practicality. Drop to a lower test frequency, which cuts the burden in proportion and is usually enough. Test the cable in sections, which halves both length and capacitance. Or move to a resonant or damped AC method, which is a different instrument family. The selector reports which of these the numbers call for.
9. Where to go next
For the test voltage itself, use the VLF test voltage calculator. For how the voltage is chosen and why it is written against U0, see VLF test voltage selection. For the rules behind the table, see what IEEE 400.2-2024 requires. For the procedure and the acceptance criteria, the VLF cable testing guide covers the test sequence end to end. Before signing a quotation, work through the VLF tester buyer’s checklist. All calculators are listed on the test instrument calculators page.
If you send us the cable schedule — voltage class, length, insulation type and the specification you are testing to — we will size the set against it and quote the configuration.