CT and PT polarity testing proves that the primary and secondary polarity marks are correct and that the secondary wiring preserves the marked direction. It verifies the polarity with a DC kick or an AC method, and confirms the effect on directional, differential, and power-measurement elements.
Key takeaways
- Polarity is a direction, not a magnitude. A reversed CT still produces the correct current magnitude; only the phase is wrong.
- P1 and S1 are the marked ends. The primary current entering P1 produces a secondary current leaving S1 in the marked direction.
- The DC kick test is the field method. A small battery and a galvanometer show the direction of the induced current when the primary circuit is made and broken.
- The AC method is the workshop method. An AC voltage on the secondary produces a voltage on the primary; the phase or the polarity is compared with the marks.
- One reversed CT can break a scheme. Directional, differential, and power elements depend on the relative polarity of several inputs.
What does a polarity test prove?
A current transformer has polarity marks P1 and P2 on the primary and S1 and S2 on the secondary. When current enters P1, the secondary current leaves S1 in the marked direction. A voltage transformer has the same convention on its primary and secondary windings.
The test proves that the physical marks match the nameplate, that the secondary wiring preserves the marked direction to the relay, and that the relay sees the correct phase relationship between the current and voltage inputs. It does not prove the ratio or the burden; test those separately.
How do you test CT and PT polarity?
- Identify the marks. Record P1/P2 and S1/S2 on the CT, and the corresponding marks on the PT. Confirm the nameplate and the scheme drawing.
- Isolate the circuit. Open the primary and secondary circuits, and confirm the isolation before connecting the test source.
- Connect the DC kick test. Connect a battery through a switch to the primary and a galvanometer to the secondary. Observe the kick when the switch is closed and opened.
- Record the direction. A kick in the marked direction confirms the polarity; a kick in the opposite direction indicates a reversed connection or a wrong mark.
- Repeat on each core. A multi-core CT has separate secondary windings; test each core and record the result.
- Test the PT. Apply a low AC voltage to the primary and measure the secondary voltage and phase, or use the AC method with a phase meter.
- Check the wiring to the relay. With the primary circuit isolated, confirm the polarity at the relay terminals, not only at the CT.
- Record the results. Note the test method, the source, the meter, and the direction for each core and phase.
What test points and acceptance criteria should you use?
| Test | Connection | Expected result | Acceptance |
|---|---|---|---|
| CT DC kick | Battery on P1-P2, galvanometer on S1-S2 | Positive kick on make | Matches the mark |
| CT DC kick, reverse | Battery reversed | Negative kick on make | Matches the mark |
| CT ratio | Primary injection | Secondary current | Within the class |
| PT ratio | Primary voltage | Secondary voltage | Within the class |
| PT phase | Phase meter | 0 or 180 degrees | Matches the mark |
| Wiring at the relay | Continuity and polarity | Correct terminal | Matches the scheme |
How do you connect the test equipment?
| Test | Equipment | Connection |
|---|---|---|
| CT DC kick | 1.5 V battery and centre-zero galvanometer | Battery to P1-P2; meter to S1-S2 |
| CT AC method | AC voltage source and voltmeter | Source to S1-S2; meter on P1-P2 |
| PT AC method | AC voltage source and phase meter | Source to primary; meter on secondary |
| Ratio | CT/PT analyzer | Primary and secondary windings |
Use a low voltage for the DC kick test; a high voltage can damage the insulation or the galvanometer. For a multi-core CT, test each core separately and record the result for each one.
What is the pass criterion?
- CT polarity: the kick direction matches the P1/S1 mark on every core.
- PT polarity: the secondary voltage is in phase or in antiphase as marked.
- Wiring: the polarity at the relay terminals matches the scheme drawing.
- Ratio: within the accuracy class, if the test includes a ratio check.
- Consistency: all phases use the same convention; a mixed convention is a failure even if each core passes on its own.
Why does a reversed polarity cause a protection problem?
Directional element. A reversed CT or PT can make the element see the fault in the opposite direction, so it trips for a reverse fault and blocks for a forward fault.
Differential element. A reversed CT on one side produces a differential current equal to twice the load current, so the relay may trip on a healthy load.
Power measurement. A reversed CT or PT makes the power measurement negative, which affects the reverse-power element and the metering.
Parallel CTs. Two CTs with opposite polarity in a parallel group produce a current that is the difference, not the sum. The relay sees a wrong current even though each CT is correct on its own.
Frequently asked questions
Why is CT polarity important?
Protection elements compare currents from different CTs. If one CT is reversed, the comparison is wrong even though each current magnitude is correct. Directional, differential, and power elements are the most sensitive.
What is the DC kick test?
A battery is connected to the primary winding through a switch, and a galvanometer is connected to the secondary. When the switch is closed, the induced current kicks in one direction; the direction confirms the polarity.
Can I test polarity with the CT in service?
No. The primary circuit must be isolated and the secondary must be disconnected from the relay. Testing in service can injure the operator and damage the relay.
What is the difference between subtractive and additive polarity?
Subtractive polarity means the primary and secondary windings are wound in the same direction, and the marked ends are at the same potential. Additive polarity is the opposite. The nameplate states the convention; do not assume one.
Do I need to test PT polarity separately from CT polarity?
Yes. A PT has its own primary and secondary marks, and the test method is different. A correct CT polarity does not prove the PT polarity.
Where VA-TEK test sets fit
The VACTP200P CT/PT analyzer performs the ratio, excitation, and polarity tests and records the result. For the relay-side check, the VAE-430 confirms the current and voltage phase relationship at the relay terminals. Start with the relay protection testing hub.
Related reading: CT/PT excitation and knee point for the excitation curve, and primary vs secondary injection testing for the injection method.
Standards and references
- IEC 61869-2:2012 — instrument transformers, current transformers.
- IEC 61869-3:2011 — instrument transformers, voltage transformers.
- IEEE C57.13-2016 — standard requirements for instrument transformers.
- Relay manufacturer’s technical manual — polarity conventions and input connections.
VACTP200P · relay protection test set
Spec the CT/PT analyzer against your test list
Ratio, excitation, polarity and winding resistance in one 9 kg case. Tell us the CT and PT classes you work with and we send the matching test templates.
- 1–30000turns ratio range
- ±0.05%ratio accuracy
- ≤40 kVknee-point test
- 9 kgcarry weight
Field-commissioning workflows, IEC and IEEE time curves, COMTRADE playback and a full DI/DO matrix — on one PC, with no per-module licence.
Request the datasheet and test templates
Tell us the CT/PT types you test. We reply with the datasheet, price and test templates within one business day.